• Designed for use in electric distribution
circuits not exceeding 600 volts phase to
phase and may be directly buried or
installed in ducts.
• May be used in wet or dry locations at
conductor temperatures not exceeding
90° C for normal operation, 130° C for
emergency overloads and 250° C under
short circuit conditions.
• Meets or exceeds industry requirements per
ASTM B-231.
• To ensure exceptional product quality,
Alcan underground 600 volt cable meets or
exceeds requirements of ICEA S-105-692.
Alcan Underground Secondary 600 Volt
Cables are constructed of:
• Hard drawn Class B stranded compressed
1350 aluminum conductors. Three quarter
hard (H26)1350 aluminum per ASTM
B609 is available upon request.
• Black crosslinked polyethylene insulation
on the phase conductors.
• TRISTRIPE® cable features a neutral
conductor that is insulated with black,
weather resistant crosslinked polyethylene
with three continuous extruded yellow
polyethylene stripes located 120° apart.
The identification stripes are weather
resistant.
• In multiplexed cable assemblies, the phase
conductors and neutral are twisted together
with a left-hand lay not greater than 60
times the outside diameter of one phase conductor.